Product Information
Description
SILENTFIX vibration isolators allow ceiling installation of pipes, ducts, heat exchangers (fans) and speakers, while avoiding the problem of transmission of generated vibrations to the structure of the building.
The SILENTFIX rubber hanger is also indispensable for the decoupling of false ceilings installed for sound insulation purposes, where rigid fixings between the suspended framework and the original ceiling have to be avoided.
The galvanised steel external structure keeps the support of the suspended loads independent of the resistance of the rubber element, thereby increasing the reliability of the installation.
Features / benefits
- load capacity range from 5 to 40 daN
- designed specifically for the isolation of hanging loads (e.g. suspended ceilings)
- highly secure fixing (separate from the rubber component)
- availability of spare parts with possible replacement of the elastomeric component alone
Materials
- Rubber: Blended rubber elastomer
- Metals: Plated steel
Loading and Dimensions
The below information is designed as a guide.
Model | Load Rating (daN) | Deflection (mm) | A | B | C (dia) | D |
V-Silentfix-4-AS | 5 - 10 | 4 - 7 | 47 | 46 | 5 | 26 |
V-Silentfix-4-N | 10 - 20 | 5.5 - 8 | 47 | 46 | 5 | 26 |
V-Silentfix-6-AS | 10 - 20 | 2.5 - 4.5 | 67 | 65 | 8 | 37 |
V-Silentfix-6-N | 20 - 40 | 2.25 - 4.75 | 67 | 65 | 8 | 37 |
Installation
Use threaded rods as per the image below. The maximum thread size for the Silentfix-4 product is M5, while the Silentfix-6 is M8. A washer must be used for the lower thread between the nut and the rubber body. This is to transfer load suitably through the rubber structure.
Lead Time
Typical lead times are 3 weeks, but this can double during summer and winter holiday seasons.